EMERGENCY
LIGHTING REGULATIONS
(Effective from 15th October 1999)
Guidance on new Regulations for Emergency Lighting
of Premises
An emergency luminaire will either be of the self-contained
type, i.e. with all components integral to the luminaire body
(battery, charging circuit, mains ballast etc), or "slave"
to a central battery system where only the lamp (and an inverter
if fluorescent) are located within the luminaire body and
the supply on power failure is fed from some centralised point.
The majority of systems installed in the United Kingdom are
of the self-contained type, but both options have their own
advantages and disadvantages. These are summarised below for
guidance:
CENTRAL BATTERY SOURCE
Advantages:
- Maintenance and routine testing is easier with only one
location to consider;
- Superior battery life, between 5 and 25 years dependant
upon type;
- Environmentally stable in a protected environment, luminaires
able to operate at relatively high or low ambient temperatures;
- Large batteries are cheaper per unit of power and luminaires
are usually less expensive.
Disadvantages:
- High capital equipment costs;
- High installation and wiring costs with essential MICC or
Pirelli FP200 type cable to each slave luminaire;
- Poor system integrity - failure of battery or wiring circuit
can disable a large part of the system;
- Requirement for 'battery room' to house cells and charger
circuits etc, may also require ventilation of acid gases;
- Localised mains failure may not trigger operation of emergency
lighting in that area.
- Voltage drop on luminaires wired furthest from the central
battery could become a problem.
SELF-CONTAINED - SINGLE POINT
Advantages:
- Speedy and low cost installation procedure;
- Standard wiring material may be used (failure of mains supply
due to cable burning through will automatically satisfy the
requirement for a luminaire to be lit);
- Low maintenance costs - periodic test and general cleaning
only required;
- Low hardware equipment costs – no requirement for
extended wiring,special ventilation etc.
- Greater system integrity with each luminaire independent
of the other;
- System can easily be extended with additional luminaires;
- No special sub-circuit monitoring requirements.
Disadvantages:
- Limited environmental operating range (batteries may be
adversely affected by a relatively high ambient temperature);
- Battery life is limited to between 2 and 4 years dependant
upon application;
- Testing requires isolation and observation of luminaires
on an individual basis.
In general then, the decision to use either a central battery
or a self-contained system is likely to be cost dominated.
If an installation has longevity and low maintenance as priorities,
then the higher cost of central battery may be acceptable
on a very large project. Usually, luminaire and installation
costs will be a major consideration, particularly on smaller
jobs, and it is this criterion which makes the self-contained
luminaire the most popular choice.
Basic Installation Design
The design of an emergency lighting scheme in the context
of BS 5266:part 1:1999, the code of practice for emergency
lighting of premises, with particular reference to the contractor
designing the installation.
What is emergency lighting?
Emergency lighting is a self-descriptive term. It is of course
lighting for an emergency, whether it be caused by fire -
when it is essential to quickly locate fire fighting equipment
and identify exit routes from the premises. Or break in the
normal lighting supplies leading to sudden darkness and the
resultant hazard to human life, either through physical danger
or panic.
Emergency lighting is normally required to operate fully
automatically and give illumination of a sufficiently high
level to enable persons of all ages to evacuate the premises
safely.
Most new buildings now have emergency lighting installed
during the course of building, the design and type of equipment
normally being specified by the relevant local authority,
Architect or Consultant.
The British Standard provides the would be emergency lighting
scheme designer with laid down guide lines which form the
general basis for him to work on. British Standard BS 5266:
part 1:1999 includes in its scope Residential Hotels, Clubs,
Hospitals, Nursing Homes, Schools and Colleges, Licensed Premises,
Offices, Museums, Shops, Multi-Storey Dwellings etc. Although
this standard recommends the types and durations of emergency
lighting systems relating to each category of premise it should
be remembered that the standards are minimum safe standards
for the types of premises and that a higher standard may be
needed for a particular installation.
Type of system
Most emergency lighting schemes fall into one of the following
categories:-
a) Non-maintained - The emergency light units only illuminate
in the event of a mains failure.
b) Maintained - The emergency light units are illuminated
at all times using the same lamps for both normal and emergency
operation.
c) Sustained - The emergency light units are fitted with 2
No. Lamps or 2 No. Sets of lamps, one of which operates on
mains 240V a.c.supply, the other which operates from the battery
supply in the event of mains failure. It is basically a non-maintained
system with the addition of mains lamps which should be illuminated
whenever the premises are occupied.
The type of system and emergency duration is often expressed
in abbreviated form as per the following examples:-
M3 - Maintained System,emergency duration 3 hours.
NM2 - Non-maintained System,emergency duration 2 hours.
S1 - Sustained System,emergency duration 1 hour.
Local regulations
Local authorities and Fire Prevention Departments quite often
publish their own recommendations regarding the types of system
and emergency durations, and these of course must be taken
into account when designing a system as they may compliment
BS 5266 or even over-ride it. It should always be borne in
mind that the system, once installed will have to comply with
the most stringent of the requirements, whether the British
Standard or the Local Authority regulations prevail.
How much light?
Having decided on your basic system consideration should now
be given to the siting of the lighting units and signs within
the particular premises involved, which will then form the
basis on which your selection of equipment can be made. The
actual degree of illumination should be closely related to
the nature of both the premises and its occupants with special
consideration being given to old persons homes, hospitals,
crowded areas such as pubs, discos and supermarkets, and to
whether or not the premises are residential.
BS5266 recommends a minimum level of only 0.2 in corridors
(permanently unobstructed) and 0.5 lux minimum for anti panic
areas to exclude 0.5 metre border around the room. (Detailed
computer point calculations or luminaire manufacturers spacing
tables should be used)
Siting of luminaires/signs
Lighting units and signs should be sited so as to clearly
show the exit routes leading to the final exits from the premises.
Where the exit route or final exit is not readily identifiable
a sign should be utilised rather than a lighting unit. Particular
attention should be paid to individual stairways, changes
in level, corridor intersections, changes in direction, the
outside of each final exit, control/plant rooms, lifts, toilet
areas over 8m (although in some peoples opinion all toilets
of public access and especially those for the disabled should
have emergency lighting).
Access to fire alarm call points, fire fighting equipment
etc. should be clearly illuminated.
In general, if common sense is used when siting the luminaires
and signs to cover these areas, then the completed scheme
will meet most requirements. Ballrooms, dancehalls, licensed
Cinemas, licensed Bingo halls and Ten Pin bowling alleys are
subject to other requirements and standards.
Guidance on new regulations for emergency lighting of premises,
Ballrooms and Dancehalls, licensed Cinemas, licensed Bingo
halls and Ten Pin bowling alleys.
This guide is based on the requirements of BS5266-1:1999
and BS5266-7:1999 (also designated as BSEN1838:1999). This
guide outlines changes to BS5266:1988 and is written in addition
to the requirements shown in detail in most Emergency Lighting
Manufacturers Catalogues.
Defined Escape Routes (Existing Buildings) For
routes that are permanently unobstructed and up to 2m wide
the horizontal illuminance at floor level on the centre line
(b) of the escape route shall be at least 0.2lux. A minimum
of 1lux is preferable and essential where there are points
of emphasis.
High Risk Task Area lighting
In areas of high risk the maintained illuminance shall not
be less than 10% of the required maintained illuminance for
the task (a desk for instance not open area). This will be
subject to a minimum illuminance of 15lux . The uniformity
ratio for task area lighting should be a minimum of 10:1 (0.1).
The minimum duration shall be the period for which the risk
exists to people.
Standby lighting
Standby lighting should comply with all emergency lighting
requirements if used for emergency lighting. Where standby
lighting is lower than maintained illuminance it should not
only be used to shut down processes.
Lighting Practices (all areas)
In order to identify safety colours, the minimum colour rendering
index for lamps used in emergency luminaries shall be 40.
The luminaire should not substantially detract from this.
Observe caution if the sole luminaire has a legend.Fluorescent
and Tungsten ra is >40.
The minimum duration for any emergency lighting luminaire
shall be 1 hour. This is increased to 2 hours in public areas
where members of the public may be unaware of emergency exit
routes or positions. In areas where dimmed lighting is used,
a maintained emergency system must be installed, in other
areas a maintained system is advantageous.
Safety Signs
The ratio to maximum and minimum luminance of a sign (on a
single colour) shall not exceed 10:1 (0.1). The ratio of the
luminaire of white parts to be coloured parts of the legend
shall not exceed 15:1 (0.06) and not be less than 5:1 (0.2).
For an internally illuminated sign the maximum viewing distance
shall be 200 times the sign height.100 times for an externally
illuminated sign.
Attention is drawn to the requirement for the format of the
sign, which should comply with the minimum requirements set
in council directive 92/58/EEC of 24 June 1992 - provision
for safety and/or Health signs at work. These signs are the
Euro legend type.
Glare Control
Emergency luminaires shall be sited in accordance with BS5266.
Attention shall be made to the manner in which luminaires
are positioned as well as luminaire type, to minimise glare.
Glare can obstruct viewing of obstructions and signs and it
is therefore important that glare is considered.
On a horizontal escape routes, open areas (anti-panic) and
High Risk areas, the luminous intensity in candelas (cd) of
the luminaire shall not exceed the values in Table 1 within
the zones 60 degrees to 90 degrees from the downward vertical
in all angles of azimuth.
For all other types of escape route the limiting values shall
not be exceeded at all angles.
|